GREI guide
RCDs in domestic installations under the GREI
The GREI requires a main RCD at the origin of the installation, then more sensitive RCDs for the most exposed circuits. Here are the rules of subsection 4.2.4.3.
The main RCD: 300 mA at most
At least one RCD of 300 mA at most is placed at the origin of the installation. It also provides isolation.
In domestic installations, all RCDs are at least type A. The one at the origin of the installation has a rated current of at least 40 A (subsection 5.3.5.3).
Its input terminals are made inaccessible: the approved body seals them during the conformity inspection.
30 mA RCDs
Directly downstream of the main RCD, at least one high or very high sensitivity RCD, that is 30 mA at most, protects at least:
- socket outlets that do not supply a fixed appliance;
- lighting;
- bathrooms and shower rooms;
- the washing machine, tumble dryer and dishwasher.
Each of these RCDs protects 8 circuits at most.
Fixed appliances, such as the fridge, the cooker or electric heating, may be connected directly under the main RCD, or under another RCD placed at the origin of the installation.
Earth electrode above 30 ohms
If the earth electrode resistance exceeds 30 ohms, at least two 30 mA RCDs are needed, and each covers at most 16 single or multiple socket outlets.
Fixed appliances connected under the main RCD then also get an RCD of 100 mA at most, per circuit or per group of circuits.
Heating in floors or walls
Electric heating with resistance elements embedded in the building structure, supplied at more than 25 V AC, is protected separately by an RCD of 100 mA at most.
An old installation
When an old domestic installation is substantially modified or extended, the whole installation is protected by at least one main RCD of 300 mA at most.
With Vonkcad
RCDs arranged and checked for you
- 300 mA at the origin and 30 mA for sockets, lighting and the bathroom, suggested automatically
- At most 8 circuits per 30 mA RCD, checked live
- Earth electrode above 30 ohms: the extra measures checked
- Earth fault simulation to see which RCD trips
Read also
The single-line diagram
What it must contain, how circuits and points are marked, the symbols.
The layout plan
The items to show, the letter-and-number marking, keeping it up to date.
The acceptance inspection
The documents to prepare, what the approved body checks, the report.
Cable size and circuit breaker
Table 4.11: the maximum rating for each cross-section, and dedicated circuits.
Sockets per circuit
At most 8 sockets per circuit, two lighting circuits, appliances on a separate circuit.
The bathroom
Zones 0, 1 and 2, permitted equipment, the RCD and equipotential bonding.
Voltage drop
What the GREI says, the 3 % and 5 % values, and the calculation with an example.
This guide summarises the GREI Book 1, 2026 version. Only the official text published by the FPS Economy is authoritative.